GensetPedia
Cummins

35 kVA Diesel Genset

35kVA prime
Prime power
75dB(A)
Noise @ 1m
CPCB IV+ compliant
Engine model
Cummins X2.6-G2, 53.1 hp certified
Alternator
STAMFORD (CGT) S1L2-J, IP23, +/-0.5% voltage regulation, Class H insulation, max 25% unbalanced load across phases
Cylinders
3, In-line - 93x127mm bore x stroke, 2590cc, 17:1 CR, G2 governing (ISO 8528-5), 12V DC electric start
Cooling
Water-cooled (radiator, EG Compleat 50:50 coolant)
Fuel tank capacity
102 L
Runtime @ 75% load
Dimensions (L×W×H)
2400 × 950 × 1400 mm
Dry weight
1,065 kg
Enclosure
Acoustic canopy (CRCA sheet, Munsell green shade; meets MoEF/CPCB norms of <=75 dB(A) at 1m at 75% load under free-field conditions; two-point top lifting, external fuel filling)
Emission norm
CPCB IV+
Control panel
Cummins PowerStart PS0602 controller: AMF, electronic governing, CAN (J1939) compatible, sync-capable, remote start/stop, Modbus RS485, sleep mode, 5-fault-code data logging, LED-backlit graphic display
Warranty
5 years (engine critical parts)
Download official spec sheet (PDF) ↓

Specifications per Cummins' official "Diesel Generator Set X2.6 Series" specification sheet (print code PSBU/CPCB IV+/X2.6/Rev-00/07 2023 -- a genuinely current, post-mandate CPCB IV+ certified product, unlike several older leaflets processed for other brands). Verified via bore x stroke x cylinder-count vs. stated displacement cross-check (93x127mm x 3-cyl = 2.59L, matched exactly). All ratings are Prime only -- no separate Standby rating stated. This document does not state a fuel-consumption L/hr figure anywhere (unusual vs. most brochures processed) -- left null rather than estimated. noise_db (75) is the brochure's stated design-compliance ceiling ("<=75 dBA @1m at 75% load"), not a certified per-unit test result. Dimensions/weight are the "Typical Enclosed Genset Dimensions" table figures (full canopy), not the smaller bare engine-skid dimensions also listed in the Engine Specification table.