Mahindra Powerol 125 kVA diesel genset
Mahindra Powerol

125 kVA Diesel Genset

125kVA prime
Prime power
21.4L/hr
Fuel @ 75% load
Emission norm not stated by manufacturer
Engine model
mPower41565G, 156 HP, TCA (Turbocharged, Charge Air-cooled), 4-cylinder variant
Alternator
CG/LS, IP23, ±1% voltage regulation, Class H insulation, 3-phase/415V, 0.8 PF lagging, max 0.25 unbalanced load across phases
Cylinders
4 - 105x137mm bore x stroke, 4800cc, G2 governing (ISO 8528 Part V), 12V DC electric start
Cooling
Water-cooled (radiator)
Fuel tank capacity
250 L
Runtime @ 75% load
~11.7 hrs
Dimensions (L×W×H)
3500 × 1230 × 1425 mm
Dry weight
1,650 kg
Enclosure
Acoustic canopy
Emission norm
Not specified (pre-2023 document)
Control panel
Microprocessor AMF
Warranty
1 yr / 2,000 hrs
Download official spec sheet (PDF) ↓

Specifications per Mahindra Powerol's dedicated official "125 kVA Diesel Genset" leaflet (print code OCT 20), cross-checked against the broader "10 kVA to 200 kVA Gensets" brochure (print code FEB 21) -- both agree exactly on engine model, HP, bore/stroke, displacement, dimensions, weight, and fuel tank capacity. This is the 4-cylinder variant (a 6-cylinder 125 kVA variant also exists, see the 125 kVA (6-cyl) listing). Additional real figures from the dedicated leaflet: fuel consumption 28 L/hr at 100% load, 13.5L total lubrication capacity (15W40 API CI4+, 500hr change interval), 19L radiator coolant capacity, 174A rated current. Neither document states a CPCB emission-norm tier, and both predate the July 2023 CPCB IV+ mandate -- confirm current compliance status with an authorized dealer before purchase. price_min/price_max and noise_db were previously carried over from this row's pre-verification placeholder seed data and are nulled here since neither brochure states them.