Mahindra Powerol 285 kVA gas genset
Mahindra Powerol

285 kVA Gas Genset

285kVA prime
Prime power
315kVA standby
Standby power
33.9kg/hr
Fuel @ 75% load
75dB(A)
Noise @ 1m
Natural GasCPCB norms compliant
Engine model
Generac G14.2L, 370 HP, Turbocharged Aftercooled, natural gas engine
Alternator
LS, IP23, ±1% voltage regulation, Class H insulation, 3-phase/415V, 0.8 PF lagging, max 25% unbalanced load across phases
Cylinders
6 - 135x165mm bore x stroke, 14200cc, G2 governing (ISO 8528 Part 5), 24V DC electric start
Cooling
Water-cooled (radiator)
Fuel tank capacity
Runtime @ 75% load
Dimensions (L×W×H)
5225 × 1700 × 3248 mm
Dry weight
6,500 kg
Enclosure
Acoustic canopy (CNC-machined parts, PU foam insulation, UV-resistant powder coating; designed to meet MoEF/CPCB norms of <=75 dB(A) at 1m at 75% load under free-field conditions)
Emission norm
CPCB norms
Control panel
Inbuilt CRCA control panel with MCCB overload/short-circuit protection; Powerzone controller with 4.3" HMI touchscreen, inbuilt Bluetooth/WiFi/LAN, Modbus remote communication, data logging and event recording
Warranty
Download official spec sheet (PDF) ↓

Specifications per Mahindra Powerol's official "285 kVA & 315 kVA Gas Gensets" leaflet (print code FEB 22). This is a dedicated natural-gas (NG) genset, not diesel -- fuel_consumption_75_lph stores kg/hr (gas is metered by mass, not volume; gas density 0.667 kg/m3 at NTP), not liters/hour. 285 kVA is the Prime rating and 315 kVA is the Standby rating for the SAME physical unit (identical engine, dimensions, and weight across both duty columns) -- unlike some diesel dual-rating brochures seen elsewhere, this one genuinely is one product at two duty points. Standby-rating (315 kVA) figures not carried by kva_prime-keyed fields: 252 kW, 438.2A, 41 kg/hr @75% load, 54.3 kg/hr @100% load. Prime-rating (285 kVA) also has 42.8 kg/hr @100% load and 396.4A, not separately tracked. No onboard fuel tank -- NG gensets run off a piped gas supply, not stored fuel, hence fuel_tank_l is null (not missing data). noise_db (75) is the canopy's CPCB/MoEF design-compliance target stated in the brochure, not a certified per-unit test result. Brochure states general CPCB-norms compliance without naming a specific tier -- confirm current status with an authorized dealer before purchase.