NewCaterpillar 1010–1100 kVA: Cat prints the diesel burn: 149.8 litres an hour at 75% load. What that means for your tank.
GensetPedia
Mahindra Powerol · M1010DR / M1250DRUpdated

Mahindra Powerol 1010 kVA & 1250 kVA DG set

Mahindra’s biggest diesel generators sit in the 1000 kVA class. The two models share one 30.5-litre Perkins engine, one frame and one canopy, but they are built for different jobs. Read the rating before you read the number.

Prime · unlimited hours
1010
kVA · 4008-30TAG2 · 1,208 BHP
Standby · 500 h a year
1250
kVA · 4008-30TAG3 · 1,481 BHP
Mahindra Powerol 1010 kVA (1000 kVA class) DG set in its acoustic canopy, left side view
Photo: Mahindra Powerol, from mahindrapowerol.com

Quick answer

  • 1010 kVA (M1010DR) is a prime rating: unlimited hours at an 80% average load.
  • 1250 kVA (M1250DR) is a standby rating: up to 500 hours a year, no overload.
  • Both use a Perkins 4008-30 engine: 8 cylinders in-line, 30.5 litres, 1500 rpm.
  • Canopied size: 6900 × 2440 × 2750 mm; weight about 10.9–11.3 tonnes.
  • Fuel tank: 990 L (integrated canopy) or 905 L (cap-on canopy).
  • Price, fuel use, noise and emission tier are not published by Mahindra.
One engine, two tunes

What is the difference between the 1010 kVA and the 1250 kVA? Same engine block, 23% more power.

Gross power+23% on the 1250
1010
1,208 BHP
1250
1,481 BHP
Net power+24% on the 1250
1010
1,140 BHP
1250
1,414 BHP
Open set wet weight+5% on the 1250
1010
7,950 kg
1250
8,340 kg

The power rises by almost a quarter while the weight rises by under 5%. That gap is what Mahindra means by “highest power to weight ratio”. The price of the extra power is the duty: the 1250 kVA rating holds for standby use only.

160 mm bore190 mm stroke× 8 in-line

π/4 × 16² × 19 cm × 8 = 30,560 cc

We checked the brochure’s 30.5 L against its own bore and stroke. It adds up.

Which one do you need?

Which rating does your site need? Move the sliders to your load.

Prime means unlimited hours at an average of 80% of the rating, with 10% extra for one hour in every twelve. Standby means up to 500 hours a year at the same 80% average, and nothing above the rating.

How will the genset run?
1010 kVA · primeavg limit 808 · rating 1010 · +10% to 1111
1250 kVA · standbyavg limit 1000 · rating 1250 · no overload
your averageyour peakwithin 80% averagerating / overload band

Both ratings cover this.

The 1250 kVA standby gives the most headroom for backup. The 1010 kVA prime also keeps you covered if outages ever run past 500 hours a year.

Large motors draw several times their running load when they start. If you have lifts, chillers or pumps, work out your peak first with the load calculator.

Footprint, drawn to scale

How big is a 1000 kVA DG set? A 20-foot container with 842 mm added on.

The dashed outline is a standard 20-ft shipping container (6058 × 2438 mm). The integrated canopy matches its width almost exactly and stands 159 mm taller. Plan the crane, the plinth and the gate around 11 tonnes.

Open set4285 × 2205 mm · 7,950–8,340 kg
20-ft container1773 mm shorter
Integrated canopy6900 × 2440 mm · 10,860–11,250 kg
20-ft container842 mm longer
Cap-on canopy6900 × 2600 mm · 10,900–11,340 kg
20-ft container842 mm longer

Both ratings share every dimension. Weights shown are 1010 kVA–1250 kVA. Fuel tank: 905 L cap-on, 990 L integrated. The open set has no tank figure in the brochure.

Inside the canopy

What comes standard with the Mahindra 1010 kVA?

Controller

DSE7320-MKII: 4-line backlit LCD, 9 inputs and 8 outputs, earth-fault trip, USB, RS232/RS485, SCADA and SMS control, PLC editor.

Remote monitoring

IoT monitoring is standard: running hours, health, rpm and error logs in an app and on the web, plus A/B-check service reminders and a log of every refuelling.

Alternator

Brushless, self-excited, Class H insulation, IP23, single sealed bearing, ±0.5% voltage regulation.

Canopy

Fire-retardant PU foam or rockwool lining, draw-out fuel tank, residential silencer. The brochure says 0–50 °C "without any deration", but its spec table adds that standard derating applies. Ask which holds.

Up to 15,000 h

between overhauls

2 years or 6,000 h

warranty (terms apply)

24 V, 2 × 180 Ah

starting system

Optional: cold-start kit, PMG alternator, space heater, RTD/BTD, AMF or ATS switching, sync controller and panel.

What the brochure does not print

What is the 1000 kVA generator price? Four things to ask before you sign

  1. 1Emission tierNo CPCB tier is stated. Ask for the CPCB certificate for M1010DR or M1250DR specifically.
  2. 2Fuel consumptionNo litres-per-hour figure at any load. Ask for it at 50%, 75% and 100%.
  3. 3NoiseNo dB(A) figure for either canopy. Ask for the test report at 1 metre.
  4. 4PriceNone published. Ask for a quote with the canopy, panel and installation listed separately.
Full specification

1010 kVA and 1250 kVA DG set specifications

1010 kVA1250 kVA
Genset
ModelM1010DRM1250DR
Rating1010 kVA (prime)1250 kVA (standby)
Open set, L × W × H4285 × 2205 × 2065 mm4285 × 2205 × 2065 mm
Cap-on canopy, L × W × H6900 × 2600 × 2750 mm6900 × 2600 × 2750 mm
Integrated canopy, L × W × H6900 × 2440 × 2750 mm6900 × 2440 × 2750 mm
Open set wet weight7,950 kg8,340 kg
Cap-on canopy weight10,900 kg11,340 kg
Integrated canopy weight10,860 kg11,250 kg
Fuel tank, cap-on / integrated905 / 990 L905 / 990 L
Governing class (ISO 8528-5)G2/G3G2/G3
Engine
Make and modelPerkins India 4008-30TAG2Perkins India 4008-30TAG3
Layout and aspiration8 cylinders in-line, TCAC8 cylinders in-line, TCAC
Gross power901 kWm / 1,208 BHP1,105 kWm / 1,481 BHP
Net power851 kWm / 1,140 BHP1,055 kWm / 1,414 BHP
Displacement30.5 L30.5 L
Bore × stroke160 × 190 mm160 × 190 mm
Speed1500 rpm1500 rpm
Compression ratio13:113:1
Lube oil, min / max127 / 153 L127 / 153 L
Coolant with radiator140 L140 L
Governor and injectionElectronic, direct injectionElectronic, direct injection
Ambient capability50 °C max (standard derating applies)50 °C max (standard derating applies)
Alternator and electrics
Output3-phase, 415 V, 4-pole3-phase, 415 V, 4-pole
Exciter and insulationBrushless, Class H (125 °C rise)Brushless, Class H (125 °C rise)
Protection and bearingIP23, single bearingIP23, single bearing
Voltage regulation± 0.5%± 0.5%
ControllerDSE7320-MKIIDSE7320-MKII
PanelsEngine control + power panelEngine control + power panel
Electrical system and battery24 V, 2 × 180 Ah24 V, 2 × 180 Ah

Values that differ between the two ratings are in bold.

Built for
  • Infrastructure
  • Industry
  • IT / ITES
  • Hospitality
  • Healthcare
  • Real estate
  • Logistics
  • Rental

Applications as listed by Mahindra Powerol.

Questions buyers ask
What is the price of a 1000 kVA generator in India?

Mahindra Powerol does not publish a price for its 1010 kVA (1000 kVA class) or 1250 kVA DG sets. The final price depends on the canopy (open, integrated or cap-on), the panel, the controller options and installation. Ask two or three sellers for a written quote with each of these listed separately; GensetPedia can help you get them on WhatsApp or email.

How much does a 1000 kVA generator weigh?

Mahindra's 1010 kVA set weighs 7,950 kg as an open set (wet), 10,860 kg with the integrated canopy and 10,900 kg with the cap-on canopy. The 1250 kVA version is 390–440 kg heavier.

What is the difference between the Mahindra Powerol 1010 kVA and 1250 kVA gensets?

Both use the same 30.5-litre, 8-cylinder Perkins 4008-30 engine and the same frame sizes. The 1010 kVA (M1010DR, engine 4008-30TAG2) is a prime rating for unlimited hours. The 1250 kVA (M1250DR, engine 4008-30TAG3, 1,481 BHP gross against 1,208) is a standby rating, limited to 500 hours a year with no overload.

Is the Mahindra 1250 kVA genset prime or standby?

Standby. Mahindra's brochure marks the 1250 kVA with an asterisk that points to its standby definition: up to 500 hours a year at an average 80% load factor, up to 300 hours of that continuously, and no overload.

Which engine does the Mahindra Powerol 1010 kVA genset use?

A Perkins India 4008-30TAG2: 8 cylinders in-line, turbocharged and aftercooled, 30.5 litres, 160 mm bore and 190 mm stroke, running at 1500 rpm with an electronic governor.

What size is a 1000 kVA DG set?

For Mahindra's 1010 kVA, the open set measures 4285 × 2205 × 2065 mm and weighs 7,950 kg wet. With the integrated canopy it is 6900 × 2440 × 2750 mm and 10,860 kg; with the cap-on canopy, 6900 × 2600 × 2750 mm and 10,900 kg.

Is the Mahindra 1010 kVA genset CPCB IV+ compliant?

The brochure does not state an emission tier, and it gives no fuel consumption or noise figures either. Ask the dealer for the CPCB certificate for the exact model before you order.

Get a dealer quote

We'll pass your details to a relevant dealer — no spam.

Compare it with other sizes on the compare tool, size your load with the load calculator, or see all Mahindra Powerol gensets.

Source & disclaimer ›

Mahindra Powerol brochure “Powering the growth journey of the nation, 1010kVA & 1250kVA” (August 2025) and the official product page. Published 24 October 2026.

GensetPedia is an independent information platform. It is not affiliated with, authorized, or endorsed by any generator manufacturer. Specifications are compiled from published brochures and public listings for reference only — always verify current specs and pricing with the dealer or manufacturer before purchase.