GensetPedia
Kirloskar / KOEL

250 kVA Diesel Genset

250kVA prime
Prime power
75dB(A)
Noise @ 1m
CPCB IV+ compliant
Engine model
Kirloskar 6SL90ETA 4G2, 228 kW (310 HP) Prime rated output at 1500 RPM, Turbocharged Aftercooled
Alternator
Brushless, Class H insulation, AREP winding (Auxiliary Regulation Excitation Principle), 94% efficiency @100% load 0.8pf, <20% max voltage dip at full load 0.8pf lag, <2 sec to build rated voltage, 415V (3P only), 50Hz
Cylinders
6, In-line - 118x135mm bore x stroke, 8.86L displacement, CRDi fuel system, G3 governing class (ISO 8528 Part V), 500hr lube oil change interval, 27L lube oil sump capacity, DOC+SCR exhaust aftertreatment with DEF/AdBlue dosing (45L tank, ISO 22241), integral set-mounted radiator tested for 50 deg C ambient, 24V DC electric start
Cooling
Liquid cooled (radiator), 36.4L coolant capacity
Fuel tank capacity
600 L
Runtime @ 75% load
Dimensions (L×W×H)
4750 × 1700 × 2005 mm
Dry weight
3,990 kg
Enclosure
Emission norm
CPCB IV+
Control panel
KG745 genset controller (used for the 6SL90 engine, distinct from the 200 kVA row's KG640C which the document states is "only for 6K Engine"): graphical LCD display, phase voltages/currents, frequency, kVA/kW/kWh/kVAr, power factor, canopy temperature (optional), lube oil pressure, engine temperature, RPM, run hours, number of starts, fuel level, auto/manual stop, battery charge condition, AMF feature; diagnostics for battery charging failure, over/under speed, over current, over/under voltage, over kW, phase sequence/missing, mains under voltage, earth fault trip, low fuel level, low lube oil pressure, high engine temperature, low/high battery voltage, over-crank protection, routine maintenance indicator, genset test facility, mains frequency; optional Modbus communication
Warranty
Download official spec sheet (PDF) ↓

Specifications per Kirloskar Oil Engines Ltd (Kirloskar Powergen)'s official "200-250 kVA CPCB IV+ Compliant" SL Series technical specification catalogue (print code 20240610/REV01/A4). Sourced from the open web (kirloskaroilengines.com) as part of a targeted search for the site's remaining zero-model brands. Verified via bore x stroke x cylinder-count vs. stated displacement cross-check (118x135mm x 6-cyl = 8.858L, matches stated 8.86L exactly). Battery starting voltage is 24V for this rating specifically (vs 12V for 200 kVA in the same document) -- a genuinely larger/different electrical starting system, not a shared value. Rated Prime only -- no Standby figure given. DOC+SCR aftertreatment with DEF/AdBlue dosing (45L tank, ISO 22241). Noise (75 dBA) is the document's own stated design ceiling. Two weight figures given (Dry, Wet w/o fuel) -- uses Dry. No fuel-consumption LPH or warranty/price figure stated.