GensetPedia
Why kW and kVAR Sharing Is Critical in Genset Synchronization
Installation & Setup

Why kW and kVAR Sharing Is Critical in Genset Synchronization

Raji Babu Naidu J

By Raji Babu Naidu J, Regional Leader — Application Engineering (MENA), Kirloskar DMCC
· 8 min read

The take

Synchronising two gensets means matching voltage, frequency, phase sequence and phase angle for the instant the breaker closes. Everything after that instant is load sharing, and it runs on two separate control loops: the governor decides how kW splits between machines, the AVR decides how kVAR splits. Get the kW loop wrong and you get overload on one set and reverse power on the other. Get the kVAR loop wrong and you get circulating reactive current and unstable voltage, often with no alarm until something trips.

When multiple gensets operate in parallel, successful synchronization is not only about matching voltage, frequency and phase angle. The real challenge is maintaining stable and balanced kW and kVAR load sharing.

I make that distinction early with almost every customer I work with, because the two things get collapsed into one. Synchronising is a condition that has to be true for a single instant — the instant the breaker closes. Load sharing is a condition that has to stay true for every hour afterwards, through every load step, every set start and stop, and every setpoint that quietly drifts between one service visit and the next. A plant can pass the first test perfectly and fail the second one for years without anybody noticing.

What makes it manageable is that the sharing problem separates cleanly into two independent control loops. Most of the confusion I see on site comes from treating them as one.

A mechanism

Why the governor stops controlling speed

On a genset running alone, the governor's job is intuitive: more fuel, more speed. That intuition breaks the moment the set is paralleled onto a bus.

Once synchronised, the machine's speed is locked to bus frequency. The other sets on the bus — and the grid, in a mains-parallel system — hold it there. Adding fuel can no longer accelerate the rotor. The energy has to go somewhere, and where it goes is real power output. The governor has quietly changed jobs, from a speed controller into a kW controller.

That is the whole basis of kW sharing:

  • It determines how the active load is distributed between gensets.
  • It is mainly controlled through the engine governor and speed control.
  • Done properly, it prevents one genset from being overloaded while another remains lightly loaded.
  • Done poorly, it leads to reverse power, overload trips and unstable operation.

Two schemes deliver it in practice. Speed droop gives each governor a setpoint that falls slightly — conventionally a few percent from no load to full load — as the machine takes kW. Since every set on the bus has to settle at the same frequency, each one ends up at the load point where its own droop line crosses that frequency. Matched droop settings and matched no-load setpoints give proportional sharing. Mismatched ones do not, and the machine with the higher effective setpoint takes the larger share whether or not that is what anyone intended.

Isochronous load sharing removes the frequency sag altogether. The controllers exchange load information — over analogue load-share lines on older plant, over a CAN link on modern controllers — and adjust fuel so that every set carries its rated proportion while bus frequency stays flat. On most installations it is the better answer, and it depends completely on that communication path being intact, correctly wired and correctly terminated.

A failure mode

Reverse power is a sharing symptom

Of the consequences of poor kW sharing, reverse power is the one I would single out, because it is the one most often misdiagnosed at site level.

If a set's governor is calling for too little fuel relative to the others, its share of kW falls — and it does not stop at zero. Past zero, the alternator stops generating and starts being driven as a motor by the rest of the bus, dragging its own engine around with it. Reverse power protection, ANSI function 32, exists precisely to catch that condition before the engine suffers for it.

The trip is genuine. The fault, usually, is not in the relay. It is a governor setpoint that has drifted, a droop percentage that does not match its twin, or an unloading ramp in the stop sequence that pushes the set into reverse power before its breaker opens. Investigating the protection instead of the sharing is one of the most reliable ways I know to spend a week and change nothing.

The mirror image is just as damaging and far quieter. The set with the higher effective setpoint absorbs a disproportionate share of every load block, runs hotter, burns more fuel, and accumulates wear that its hour meter alone will never explain. Where nobody has compared the two kW readings under load, this can continue for years. It is the control-side counterpart of a problem GensetPedia has covered on the operating side — having two gensets installed does not mean both should be running.

A second loop

What the AVR is actually doing

Reactive power gets far less attention than kW, largely because it does no useful work. It magnetises motors and transformers and moves back and forth without being consumed. But it flows through the same windings and the same cables as real power, and it has to be shared just as deliberately.

The excitation loop mirrors the governor loop almost exactly. On an isolated alternator, more excitation means more terminal voltage. Paralleled, terminal voltage is the bus voltage, and every machine on the bus is holding it. Raising excitation on one machine can no longer lift bus voltage by itself — instead, that machine takes a bigger share of the reactive load. The AVR has changed jobs in the same way the governor did, from a voltage controller into a kVAR controller.

The reactive side, stated the same way:

  • It determines how reactive load is distributed between gensets.
  • It is mainly controlled through the AVR and excitation system.
  • Done properly, it maintains voltage stability and prevents excessive circulating reactive current.
  • Done poorly, one generator takes excessive reactive load while another operates at low or negative kVAR.

That last point describes the characteristic failure, and it is worth picturing. One machine is over-excited and heavily lagging. Another is under-excited, possibly leading — importing reactive power from its neighbour rather than supplying any. The reactive current circulating between them serves no load at all. It heats both alternators, consumes capacity that could have gone to real work, and leaves voltage regulation twitchy through load steps. In severe cases the under-excited machine approaches its stability limit, and loss-of-excitation protection, ANSI 40, has something to say about it.

The two schemes here parallel the governor's. Reactive droop compensation — often called voltage droop, or referred to by the paralleling CT it needs — feeds each AVR a signal proportional to its own reactive current, so its voltage setpoint falls slightly as it takes kVAR, exactly as speed droop works for kW. Cross-current compensation interconnects the AVRs so that only the difference in reactive current between machines acts on excitation, sharing kVAR without any droop in bus voltage at all.

A summary worth memorising

Two loops, two stabilities

For stable parallel operation, this is the relationship I would ask anyone to hold in mind:

Governor → kW Sharing   → Frequency Stability
AVR      → kVAR Sharing → Voltage Stability

Frequency is a real-power phenomenon. Voltage is a reactive-power phenomenon. When a paralleled plant hunts on frequency, the cause sits on the governor side of that table. When it hunts on voltage, it sits on the AVR side. Knowing which column a symptom belongs to eliminates half the possible causes before anyone opens a panel door, and it is the single most useful habit I can pass on to an engineer new to parallel systems.

A checklist

What actually has to be right

Six things have to be correct for stable parallel operation, and each of them is a place I have seen commissioning go wrong:

  • Correct controller configuration. Rating, CT ratio, droop mode and load-share scheme have to match the machine they are configured on — not the machine the settings were copied from.
  • Proper governor response. Sharing that is correct in steady state can still be unstable through a load step if the response is too slow or too aggressive.
  • AVR stability and droop settings. The same applies on the reactive side, with the added trap that a poor droop setting can look perfectly fine at no load and diverge only once reactive load appears.
  • Accurate CT/PT polarity and sensing. This is the classic one. Droop compensation depends on the sign of the reactive current signal. Reverse that CT and the correction pushes sharing apart instead of pulling it together — the machine already taking too much kVAR takes more. It is a wiring error that presents itself as a control instability, which is why it costs so much time.
  • Correct generator ratings and operating parameters. Sets of different ratings must share in proportion to their ratings; scaling that wrongly guarantees one machine reaches its limit first.
  • Proper load-sharing communication. Analogue load-share lines and CAN links both need correct wiring, screening and termination. A degraded link does not always fail cleanly — it can share badly rather than not at all, which is the harder failure to spot.

None of these are exotic. They are the things that get assumed rather than verified, particularly when a second set is added years after the first and the commissioning of the original machine is nobody's living memory.

A takeaway

Closing the breaker is the beginning

Synchronizing is only the beginning. Stable kW and kVAR sharing is what makes multiple gensets operate safely and reliably in parallel.

A paralleling relay confirms one instant. Load sharing has to hold for every hour after it. So if your site runs sets in parallel, the two most informative numbers on the controller are not on the synchroscope — they are the kW and kVAR readings on each machine, under load, compared against each other. If they do not sit in proportion to the machines' ratings, the plant is already telling you which of the two loops to look at first.

Good engineering here is not really about the sophistication of the controller. It is about verifying the handful of things that decide whether two machines cooperate or quietly fight each other.

Raji Babu Naidu J leads Application Engineering for the MENA region at Kirloskar and has 17+ years of experience in diesel engines, generator sets and industrial power systems across India, the GCC and international markets, including hands-on work with DSE, ComAp, DEIF, Woodward and GAC control systems. This article is contributed to GensetPedia in a personal capacity; the views expressed are the author's own and not those of any employer. Load-sharing, droop and protection settings are specific to your machines, controllers and installation — confirm any change with your genset manufacturer, panel supplier or commissioning engineer before altering a commissioned setup.

Why it matters

A parallel installation that synchronises cleanly on the commissioning day can still be sharing load badly for years. Unequal kW sharing quietly overloads one engine while the other coasts or motors; unequal kVAR sharing pushes circulating current between alternators that does no useful work but heats windings and drags voltage around. Neither shows up as an obvious fault — they show up as one set reaching overhaul far ahead of its twin, as nuisance reverse-power and over-excitation trips during load steps, and as a plant that nobody trusts to run in parallel when it actually matters.

Raji Babu Naidu J

About the author

Raji Babu Naidu J

Regional Leader — Application Engineering (MENA), Kirloskar DMCC

Dubai, United Arab Emirates

Frequently asked questions

What is kW and kVAR sharing in genset parallel operation?+

It is how two or more gensets running in parallel divide the load between them. kW sharing is the split of real (active) power — the part that does actual work — and it is controlled by each engine's governor or speed control. kVAR sharing is the split of reactive power, which magnetises motors and transformers, and it is controlled by each alternator's AVR and excitation system. Synchronising only gets the machines onto the same bus; kW and kVAR sharing is what keeps them there stably.

What controls kW sharing between gensets?+

The engine governor. On a machine already synchronised to a bus, adding fuel cannot make the alternator spin faster — the bus frequency holds it — so extra fuel shows up as extra real power output instead. Governors achieve sharing either through speed droop, where each set's speed setpoint falls slightly as it takes load so the machines settle at a common frequency, or through isochronous load sharing, where the controllers exchange load information over analogue load-share lines or a CAN link and hold frequency flat while splitting kW in proportion to rating.

What controls kVAR sharing between gensets?+

The AVR and excitation system. Once paralleled, raising an alternator's excitation does not raise bus voltage on its own — it makes that machine take a larger share of the reactive load. Sharing is achieved either through reactive droop compensation, where a sensing CT lets each AVR reduce its voltage setpoint slightly as it takes reactive load, or through cross-current compensation, where AVRs are interconnected so only the difference between machines acts on excitation.

What causes reverse power trips on a paralleled genset?+

Reverse power means the alternator has stopped generating and is being driven as a motor by the bus, which happens when its engine is delivering too little fuel relative to the others — a governor setpoint that has drifted low, mismatched droop settings between sets, or an unloading sequence that pulls one set below zero before its breaker opens. Reverse power protection, ANSI function 32, trips to protect the engine, so repeated trips are usually a kW-sharing symptom rather than a faulty relay.

Do gensets in parallel need to be the same brand and rating?+

They do not need to be identical, but they do need compatible controls and correctly configured settings. Sets of different ratings share load in proportion to their ratings rather than equally, so droop and load-share settings must be scaled to each machine. Mixing controller families or excitation schemes is possible but adds commissioning work, which is why parallel-capable installations are usually specified with a common controller platform and a defined load-sharing scheme from the start.

Found this useful?

Follow GensetPedia on LinkedIn for more genset buying guides and industry data.

Follow us

Get the weekly digest

New buying guides and market data, once a week — no spam.

Related reading