NewCaterpillar 1010–1100 kVA: Cat prints the diesel burn: 149.8 litres an hour at 75% load. What that means for your tank.
GensetPedia

Mahindra Powerol

15 kVA Diesel Genset (3255)

3255 GM-C2, 25 HP, Naturally Aspirated

Prime
15kVA
Fuel @ 75%
3L/hr
Weight
738kg
Fuel tank
75L
Emission norm not stated by manufacturer
Mahindra PowerolRating plate
Output
15 kVA · 12 kW
Engine
3255 GM-C2, 25 HP, Naturally Aspirated
Alternator
CG/LS, IP23, ±1% voltage regulation, Class H insulation
Cooling
Water-cooled (radiator)

Specifications

Mahindra Powerol 15 kVA specifications

Engine and alternator

Engine model
3255 GM-C2, 25 HP, Naturally Aspirated
Cylinders
3 - 88.9x110mm bore x stroke, 2048cc
Alternator
CG/LS, IP23, ±1% voltage regulation, Class H insulation
Cooling
Water-cooled (radiator)
Control panel
Microprocessor AMF

Fuel

Fuel tank capacity
75 L
Fuel use @ 75% load
3 L/hr
Runtime @ 75% load
~25.0 hours

Size and build

Dimensions (L × W × H)
1875 × 900 × 1287 mm
Dry weight
738 kg
Enclosure
Acoustic canopy
Noise @ 1 m
Not published by the maker

Compliance and warranty

Emission norm
Not specified (pre-2023 document)
Warranty
1 yr / 2,000 hrs
Indicative price
Not published by the maker
Source & notes ›

Specifications per Mahindra Powerol's official "10 kVA to 200 kVA Gensets" brochure (print code: FEB 21). Document does not state a CPCB emission-norm tier and predates the July 2023 CPCB IV+ mandate -- confirm current compliance status with an authorized dealer before purchase.

Read before you buy

Compare with similar models